{"id":1307,"date":"2026-07-22T05:33:10","date_gmt":"2026-07-22T05:33:10","guid":{"rendered":"https:\/\/lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/"},"modified":"2026-09-28T01:01:30","modified_gmt":"2026-09-28T01:01:30","slug":"how-is-the-induced-voltage-withstand-test-for-transformers-conducted","status":"publish","type":"post","link":"https:\/\/www.lstransformer.com\/de\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/","title":{"rendered":"How is the Induced Voltage Withstand Test for Transformers conducted?"},"content":{"rendered":"<h1 style=\"text-align: left;\">How is the Induced Voltage Withstand Test for Transformers conducted?<b><\/b><\/h1>\n<p>The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage when unsaturated, thereby testing the insulation performance of winding-to-winding, layer-to-layer, and phase-to-phase. This evaluates the longitudinal insulation level of the transformer.<\/p>\n<p>For transformers with graded insulation, raising the neutral point voltage (supporting it) allows the assessment of the main insulation level. Consequently, the Induced Voltage Withstand Test not only tests the longitudinal insulation but also compensates for the inability of such transformers to undergo an External Withstand Voltage Test, effectively performing an equivalent external test.<\/p>\n<p>In the case of a three-phase transformer with graded insulation, the Induced Voltage Withstand Test typically employs a phase-by-phase induction test method. The non-tested two phases (B, C phases in the diagram) are connected in parallel and grounded at the line end, while the neutral point (0) is raised to approximately 1\/3 of the test voltage. This ensures that the line end of the test phase (A phase in the diagram) meets the requirements of an External Withstand Voltage Test, and the induced voltage of the test phase winding meets the requirements of the induction test.<\/p>\n<p>If such adjustments cannot meet the test requirements, the tap position can be adjusted, or another transformer can be used as a supporting transformer to support the neutral point.<\/p>\n<p>According to the requirements of the new standard, during the induction test, it is necessary to measure the local discharge quantity as well as the starting and extinguishing voltages of local discharge.<\/p>\n<h2 style=\"font-weight: bold;\">Kontakt<\/h2>\n<p>\u96fb\u529b\u306e\u7b97\u51fa: <a href=\"https:\/\/www.lstransformer.com\/de\/\">single-phase transformer, three-phase-isolation in Transformatoren, elektrischen Transformator, Verteilung Transformator, step-down und step-up-Transformator, low-Spannung Transformator, hohe Spannung Transformator, Steuerung, Transformator, Ringkern Transformator, R-core-Transformator; DC-Spulen, AC Reaktoren, Filter-Reaktor -, line-und load reactor, drosseln, Filter-Reaktor, und die Mittel, hoch-Frequenz-Produkte<\/a>.<\/p>\n<p>\u304cV_peak\u7a4d\u306e\u904e\u96fb\u5727\u306e\u30d4\u30fc\u30af\u3068t_res\u306b\u5171\u9cf4\u3002 30%\u30de\u30fc\u30b8\u30f3\u63a8\u5968\u3092\u5360\u3081\u308b\u30b7\u30b9\u30c6\u30e0\u30d1\u30e9\u30e1\u30fc\u30bf\u5316\u3057\u307e\u3059\u3002<\/p>\n<p>2.2.3\u306e\u52d5\u7684\u5fdc\u7b54\u30bd\u30ea\u30e5\u30fc\u30b7\u30e7\u30f3 <a href=\"https:\/\/www.lstransformer.com\/de\/\">\u73fe\u4ee3\u306e\u30b7\u30b9\u30c6\u30e0\u5229\u7528\u30b5\u30a4\u30ea\u30b9\u30bf\u5236\u5fa1\u306b\u3088\u308b\u62b5\u6297\u6e1b\u8870(TCRD)\u3092\u691c\u77e5\u3059\u308b\u5171\u9cf4\u518510ms\u3001\u914d\u306e\u6b63\u78ba\u6027\u3001\u5207\u65ad\u4e2d\u306e\u901a\u5e38\u306e\u64cd\u4f5c\u306f\u907f\u3051\u307e\u3059\u3002<\/a>.<\/p>\n<p>3. \u9023\u643a\u6a5f\u69cb\u306e\u30a2\u30af\u30c6\u30a3\u30d6\u30d5\u30a3\u30eb\u30bf<br \/>\nWhatsApp\uff1a+86 13787095096<br \/>\nE-Mail: marketing@hnlsdz.com<\/p>","protected":false},"excerpt":{"rendered":"<p>How is the Induced Voltage Withstand Test for Transformers conducted? The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage [&hellip;]<\/p>\n","protected":false},"author":3,"featured_media":4174,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"default","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"footnotes":""},"categories":[48],"tags":[],"class_list":["post-1307","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-faq"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.1 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>How is the Induced Voltage Withstand Test for Transformers conducted? - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD<\/title>\n<meta name=\"description\" content=\"The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage when unsaturated, thereby testing the insulation performance of winding-to-winding, layer-to-layer, and phase-to-phase. This evaluates the longitudinal insulation level of the transformer.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.lstransformer.com\/de\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/\" \/>\n<meta property=\"og:locale\" content=\"de_DE\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"How is the Induced Voltage Withstand Test for Transformers conducted? - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\" \/>\n<meta property=\"og:description\" content=\"The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage when unsaturated, thereby testing the insulation performance of winding-to-winding, layer-to-layer, and phase-to-phase. This evaluates the longitudinal insulation level of the transformer.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.lstransformer.com\/de\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/\" \/>\n<meta property=\"og:site_name\" content=\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\" \/>\n<meta property=\"article:published_time\" content=\"2026-07-22T05:33:10+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-09-28T01:01:30+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742019121228894.png\" \/>\n\t<meta property=\"og:image:width\" content=\"370\" \/>\n\t<meta property=\"og:image:height\" content=\"276\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"369703005\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Verfasst von\" \/>\n\t<meta name=\"twitter:data1\" content=\"369703005\" \/>\n\t<meta name=\"twitter:label2\" content=\"Gesch\u00e4tzte Lesezeit\" \/>\n\t<meta name=\"twitter:data2\" content=\"3\u00a0Minuten\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/\"},\"author\":{\"name\":\"369703005\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/person\\\/674089c15f4857c19a997f886816d289\"},\"headline\":\"How is the Induced Voltage Withstand Test for Transformers conducted?\",\"datePublished\":\"2026-07-22T05:33:10+00:00\",\"dateModified\":\"2026-09-28T01:01:30+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/\"},\"wordCount\":422,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#organization\"},\"image\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742019121228894.png\",\"articleSection\":[\"FAQ\"],\"inLanguage\":\"de\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/\",\"name\":\"How is the Induced Voltage Withstand Test for Transformers conducted? - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742019121228894.png\",\"datePublished\":\"2026-07-22T05:33:10+00:00\",\"dateModified\":\"2026-09-28T01:01:30+00:00\",\"description\":\"The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage when unsaturated, thereby testing the insulation performance of winding-to-winding, layer-to-layer, and phase-to-phase. This evaluates the longitudinal insulation level of the transformer.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#breadcrumb\"},\"inLanguage\":\"de\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"de\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742019121228894.png\",\"contentUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742019121228894.png\",\"width\":370,\"height\":276},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"\u9996\u9875\",\"item\":\"https:\\\/\\\/www.lstransformer.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"How is the Induced Voltage Withstand Test for Transformers conducted?\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#website\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/\",\"name\":\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\",\"description\":\"\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.lstransformer.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"de\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#organization\",\"name\":\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"de\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/06\\\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp\",\"contentUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/06\\\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp\",\"width\":760,\"height\":202,\"caption\":\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\"},\"image\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/logo\\\/image\\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/person\\\/674089c15f4857c19a997f886816d289\",\"name\":\"369703005\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"de\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g\",\"caption\":\"369703005\"},\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/de\\\/author\\\/369703005\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"How is the Induced Voltage Withstand Test for Transformers conducted? - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","description":"The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage when unsaturated, thereby testing the insulation performance of winding-to-winding, layer-to-layer, and phase-to-phase. This evaluates the longitudinal insulation level of the transformer.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.lstransformer.com\/de\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/","og_locale":"de_DE","og_type":"article","og_title":"How is the Induced Voltage Withstand Test for Transformers conducted? - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","og_description":"The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage when unsaturated, thereby testing the insulation performance of winding-to-winding, layer-to-layer, and phase-to-phase. This evaluates the longitudinal insulation level of the transformer.","og_url":"https:\/\/www.lstransformer.com\/de\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/","og_site_name":"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","article_published_time":"2026-07-22T05:33:10+00:00","article_modified_time":"2026-09-28T01:01:30+00:00","og_image":[{"width":370,"height":276,"url":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742019121228894.png","type":"image\/png"}],"author":"369703005","twitter_card":"summary_large_image","twitter_misc":{"Verfasst von":"369703005","Gesch\u00e4tzte Lesezeit":"3\u00a0Minuten"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#article","isPartOf":{"@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/"},"author":{"name":"369703005","@id":"https:\/\/www.lstransformer.com\/#\/schema\/person\/674089c15f4857c19a997f886816d289"},"headline":"How is the Induced Voltage Withstand Test for Transformers conducted?","datePublished":"2026-07-22T05:33:10+00:00","dateModified":"2026-09-28T01:01:30+00:00","mainEntityOfPage":{"@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/"},"wordCount":422,"commentCount":0,"publisher":{"@id":"https:\/\/www.lstransformer.com\/#organization"},"image":{"@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#primaryimage"},"thumbnailUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742019121228894.png","articleSection":["FAQ"],"inLanguage":"de","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/","url":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/","name":"How is the Induced Voltage Withstand Test for Transformers conducted? - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","isPartOf":{"@id":"https:\/\/www.lstransformer.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#primaryimage"},"image":{"@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#primaryimage"},"thumbnailUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742019121228894.png","datePublished":"2026-07-22T05:33:10+00:00","dateModified":"2026-09-28T01:01:30+00:00","description":"The Induced Voltage Withstand Test for fully insulated transformers is conducted by opening the high-voltage winding and applying twice the rated voltage at a frequency of 100-250Hz to the low-voltage winding. Due to the higher frequency, the iron core can ensure twice the induced voltage when unsaturated, thereby testing the insulation performance of winding-to-winding, layer-to-layer, and phase-to-phase. This evaluates the longitudinal insulation level of the transformer.","breadcrumb":{"@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#breadcrumb"},"inLanguage":"de","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/"]}]},{"@type":"ImageObject","inLanguage":"de","@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#primaryimage","url":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742019121228894.png","contentUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742019121228894.png","width":370,"height":276},{"@type":"BreadcrumbList","@id":"https:\/\/www.lstransformer.com\/how-is-the-induced-voltage-withstand-test-for-transformers-conducted\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"\u9996\u9875","item":"https:\/\/www.lstransformer.com\/"},{"@type":"ListItem","position":2,"name":"How is the Induced Voltage Withstand Test for Transformers conducted?"}]},{"@type":"WebSite","@id":"https:\/\/www.lstransformer.com\/#website","url":"https:\/\/www.lstransformer.com\/","name":"LS power Transformator, die Linie Reaktor, Hohe-Spannung Transformator, \u00d6l-eingetaucht Transformator-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","description":"","publisher":{"@id":"https:\/\/www.lstransformer.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.lstransformer.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"de"},{"@type":"Organization","@id":"https:\/\/www.lstransformer.com\/#organization","name":"LS power Transformator, die Linie Reaktor, Hohe-Spannung Transformator, \u00d6l-eingetaucht Transformator-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","url":"https:\/\/www.lstransformer.com\/","logo":{"@type":"ImageObject","inLanguage":"de","@id":"https:\/\/www.lstransformer.com\/#\/schema\/logo\/image\/","url":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/06\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp","contentUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/06\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp","width":760,"height":202,"caption":"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD"},"image":{"@id":"https:\/\/www.lstransformer.com\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/www.lstransformer.com\/#\/schema\/person\/674089c15f4857c19a997f886816d289","name":"369703005","image":{"@type":"ImageObject","inLanguage":"de","@id":"https:\/\/secure.gravatar.com\/avatar\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g","caption":"369703005"},"url":"https:\/\/www.lstransformer.com\/de\/author\/369703005\/"}]}},"_links":{"self":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts\/1307","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/users\/3"}],"replies":[{"embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/comments?post=1307"}],"version-history":[{"count":4,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts\/1307\/revisions"}],"predecessor-version":[{"id":6723,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts\/1307\/revisions\/6723"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/media\/4174"}],"wp:attachment":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/media?parent=1307"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/categories?post=1307"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/tags?post=1307"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}