{"id":1329,"date":"2026-07-22T05:33:12","date_gmt":"2026-07-22T05:33:12","guid":{"rendered":"https:\/\/lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/"},"modified":"2026-09-28T02:48:42","modified_gmt":"2026-09-28T02:48:42","slug":"whats-thepurpose-and-significance-of-partial-discharge-testing","status":"publish","type":"post","link":"https:\/\/www.lstransformer.com\/de\/whats-thepurpose-and-significance-of-partial-discharge-testing\/","title":{"rendered":"What\u2019s the Purpose and Significance of Partial Discharge Testing"},"content":{"rendered":"<h1 style=\"text-align: left;\">What\u2019s the\u00a0Purpose and Significance of Partial Discharge Testing<b><\/b><\/h1>\n<p>Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge manifests as breakdown of insulation gas, local breakdown of solid or liquid media within a small range, and local breakdown discharge caused by the concentration of electric field strength at the edges and corners of metal surfaces. Although the energy of this discharge is small, its short-term existence does not affect the insulation strength of electrical equipment. However, if partial discharge occurs continuously under the operating voltage of electrical equipment, these weak discharges will accumulate, gradually deteriorating the dielectric performance of insulation and enlarging local defects, ultimately leading to insulation breakdown.<\/p>\n<p>Traditional insulation test methods are difficult to detect partial discharge defects, and a 1-minute AC withstand voltage test can damage insulation, affecting the subsequent operational performance of the equipment.<\/p>\n<p>Under the influence of partial discharge, oil-paper insulation generates unsaturated hydrocarbons such as C2H2 (acetylene) and wax. The wax accumulates on solid insulation, and the gas generated by the discharge increases the discharge, leading to breakdown at positions with high field strength or damaged portions of insulating paper. This may manifest as creeping discharge in inter-layer gaps, the formation of branched discharge, and the formation of orderly carbonization layers on discharge channels, eventually penetrating the insulation.<\/p>\n<p>Although partial discharge can lead to insulation deterioration and eventual damage, its development takes a certain amount of time. The development time depends on various factors such as the operating condition of the equipment itself, the type of partial discharge, the occurrence location, and the insulation structure of the equipment.<\/p>\n<h2 style=\"font-weight: bold;\">Kontakt<\/h2>\n<p>\u96fb\u529b\u306e\u7b97\u51fa: <a href=\"https:\/\/www.lstransformer.com\/de\/\">single-phase transformer, three-phase-isolation in Transformatoren, elektrischen Transformator, Verteilung Transformator, step-down und step-up-Transformator, low-Spannung Transformator, hohe Spannung Transformator, Steuerung, Transformator, Ringkern Transformator, R-core-Transformator; DC-Spulen, AC Reaktoren, Filter-Reaktor -, line-und load reactor, drosseln, Filter-Reaktor, und die Mittel, hoch-Frequenz-Produkte<\/a>.<\/p>\n<p>\u304cV_peak\u7a4d\u306e\u904e\u96fb\u5727\u306e\u30d4\u30fc\u30af\u3068t_res\u306b\u5171\u9cf4\u3002 30%\u30de\u30fc\u30b8\u30f3\u63a8\u5968\u3092\u5360\u3081\u308b\u30b7\u30b9\u30c6\u30e0\u30d1\u30e9\u30e1\u30fc\u30bf\u5316\u3057\u307e\u3059\u3002<\/p>\n<p>2.2.3\u306e\u52d5\u7684\u5fdc\u7b54\u30bd\u30ea\u30e5\u30fc\u30b7\u30e7\u30f3 <a href=\"https:\/\/www.lstransformer.com\/de\/\">\u73fe\u4ee3\u306e\u30b7\u30b9\u30c6\u30e0\u5229\u7528\u30b5\u30a4\u30ea\u30b9\u30bf\u5236\u5fa1\u306b\u3088\u308b\u62b5\u6297\u6e1b\u8870(TCRD)\u3092\u691c\u77e5\u3059\u308b\u5171\u9cf4\u518510ms\u3001\u914d\u306e\u6b63\u78ba\u6027\u3001\u5207\u65ad\u4e2d\u306e\u901a\u5e38\u306e\u64cd\u4f5c\u306f\u907f\u3051\u307e\u3059\u3002<\/a>.<\/p>\n<p>3. \u9023\u643a\u6a5f\u69cb\u306e\u30a2\u30af\u30c6\u30a3\u30d6\u30d5\u30a3\u30eb\u30bf<br \/>\nWhatsApp\uff1a+86 13787095096<br \/>\nE-Mail: marketing@hnlsdz.com<\/p>","protected":false},"excerpt":{"rendered":"<p>What\u2019s the\u00a0Purpose and Significance of Partial Discharge Testing Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge [&hellip;]<\/p>\n","protected":false},"author":3,"featured_media":4191,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"default","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"footnotes":""},"categories":[48],"tags":[],"class_list":["post-1329","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-faq"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.1 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>What\u2019s the Purpose and Significance of Partial Discharge Testing - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD<\/title>\n<meta name=\"description\" content=\"Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge manifests as breakdown of insulation gas, local breakdown of solid or liquid media within a small range, and local breakdown discharge caused by the concentration of electric field strength at the edges and corners of metal surfaces. Although the energy of this discharge is small, its short-term existence does not affect the insulation strength of electrical equipment. However, if partial discharge occurs continuously under the operating voltage of electrical equipment, these weak discharges will accumulate, gradually deteriorating the dielectric performance of insulation and enlarging local defects, ultimately leading to insulation breakdown.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.lstransformer.com\/de\/whats-thepurpose-and-significance-of-partial-discharge-testing\/\" \/>\n<meta property=\"og:locale\" content=\"de_DE\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"What\u2019s the Purpose and Significance of Partial Discharge Testing - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\" \/>\n<meta property=\"og:description\" content=\"Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge manifests as breakdown of insulation gas, local breakdown of solid or liquid media within a small range, and local breakdown discharge caused by the concentration of electric field strength at the edges and corners of metal surfaces. Although the energy of this discharge is small, its short-term existence does not affect the insulation strength of electrical equipment. However, if partial discharge occurs continuously under the operating voltage of electrical equipment, these weak discharges will accumulate, gradually deteriorating the dielectric performance of insulation and enlarging local defects, ultimately leading to insulation breakdown.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.lstransformer.com\/de\/whats-thepurpose-and-significance-of-partial-discharge-testing\/\" \/>\n<meta property=\"og:site_name\" content=\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\" \/>\n<meta property=\"article:published_time\" content=\"2026-07-22T05:33:12+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-09-28T02:48:42+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742021235912180.png\" \/>\n\t<meta property=\"og:image:width\" content=\"370\" \/>\n\t<meta property=\"og:image:height\" content=\"276\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"369703005\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Verfasst von\" \/>\n\t<meta name=\"twitter:data1\" content=\"369703005\" \/>\n\t<meta name=\"twitter:label2\" content=\"Gesch\u00e4tzte Lesezeit\" \/>\n\t<meta name=\"twitter:data2\" content=\"3\u00a0Minuten\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/\"},\"author\":{\"name\":\"369703005\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/person\\\/674089c15f4857c19a997f886816d289\"},\"headline\":\"What\u2019s the Purpose and Significance of Partial Discharge Testing\",\"datePublished\":\"2026-07-22T05:33:12+00:00\",\"dateModified\":\"2026-09-28T02:48:42+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/\"},\"wordCount\":440,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#organization\"},\"image\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742021235912180.png\",\"articleSection\":[\"FAQ\"],\"inLanguage\":\"de\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/\",\"name\":\"What\u2019s the Purpose and Significance of Partial Discharge Testing - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742021235912180.png\",\"datePublished\":\"2026-07-22T05:33:12+00:00\",\"dateModified\":\"2026-09-28T02:48:42+00:00\",\"description\":\"Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge manifests as breakdown of insulation gas, local breakdown of solid or liquid media within a small range, and local breakdown discharge caused by the concentration of electric field strength at the edges and corners of metal surfaces. Although the energy of this discharge is small, its short-term existence does not affect the insulation strength of electrical equipment. However, if partial discharge occurs continuously under the operating voltage of electrical equipment, these weak discharges will accumulate, gradually deteriorating the dielectric performance of insulation and enlarging local defects, ultimately leading to insulation breakdown.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#breadcrumb\"},\"inLanguage\":\"de\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"de\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742021235912180.png\",\"contentUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/07\\\/1742021235912180.png\",\"width\":370,\"height\":276},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/whats-thepurpose-and-significance-of-partial-discharge-testing\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"\u9996\u9875\",\"item\":\"https:\\\/\\\/www.lstransformer.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"What\u2019s the Purpose and Significance of Partial Discharge Testing\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#website\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/\",\"name\":\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\",\"description\":\"\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.lstransformer.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"de\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#organization\",\"name\":\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"de\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/06\\\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp\",\"contentUrl\":\"https:\\\/\\\/www.lstransformer.com\\\/wp-content\\\/uploads\\\/2026\\\/06\\\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp\",\"width\":760,\"height\":202,\"caption\":\"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD\"},\"image\":{\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/logo\\\/image\\\/\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.lstransformer.com\\\/#\\\/schema\\\/person\\\/674089c15f4857c19a997f886816d289\",\"name\":\"369703005\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"de\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g\",\"caption\":\"369703005\"},\"url\":\"https:\\\/\\\/www.lstransformer.com\\\/de\\\/author\\\/369703005\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"What\u2019s the Purpose and Significance of Partial Discharge Testing - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","description":"Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge manifests as breakdown of insulation gas, local breakdown of solid or liquid media within a small range, and local breakdown discharge caused by the concentration of electric field strength at the edges and corners of metal surfaces. Although the energy of this discharge is small, its short-term existence does not affect the insulation strength of electrical equipment. However, if partial discharge occurs continuously under the operating voltage of electrical equipment, these weak discharges will accumulate, gradually deteriorating the dielectric performance of insulation and enlarging local defects, ultimately leading to insulation breakdown.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.lstransformer.com\/de\/whats-thepurpose-and-significance-of-partial-discharge-testing\/","og_locale":"de_DE","og_type":"article","og_title":"What\u2019s the Purpose and Significance of Partial Discharge Testing - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","og_description":"Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge manifests as breakdown of insulation gas, local breakdown of solid or liquid media within a small range, and local breakdown discharge caused by the concentration of electric field strength at the edges and corners of metal surfaces. Although the energy of this discharge is small, its short-term existence does not affect the insulation strength of electrical equipment. However, if partial discharge occurs continuously under the operating voltage of electrical equipment, these weak discharges will accumulate, gradually deteriorating the dielectric performance of insulation and enlarging local defects, ultimately leading to insulation breakdown.","og_url":"https:\/\/www.lstransformer.com\/de\/whats-thepurpose-and-significance-of-partial-discharge-testing\/","og_site_name":"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","article_published_time":"2026-07-22T05:33:12+00:00","article_modified_time":"2026-09-28T02:48:42+00:00","og_image":[{"width":370,"height":276,"url":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742021235912180.png","type":"image\/png"}],"author":"369703005","twitter_card":"summary_large_image","twitter_misc":{"Verfasst von":"369703005","Gesch\u00e4tzte Lesezeit":"3\u00a0Minuten"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#article","isPartOf":{"@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/"},"author":{"name":"369703005","@id":"https:\/\/www.lstransformer.com\/#\/schema\/person\/674089c15f4857c19a997f886816d289"},"headline":"What\u2019s the Purpose and Significance of Partial Discharge Testing","datePublished":"2026-07-22T05:33:12+00:00","dateModified":"2026-09-28T02:48:42+00:00","mainEntityOfPage":{"@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/"},"wordCount":440,"commentCount":0,"publisher":{"@id":"https:\/\/www.lstransformer.com\/#organization"},"image":{"@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#primaryimage"},"thumbnailUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742021235912180.png","articleSection":["FAQ"],"inLanguage":"de","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/","url":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/","name":"What\u2019s the Purpose and Significance of Partial Discharge Testing - LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","isPartOf":{"@id":"https:\/\/www.lstransformer.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#primaryimage"},"image":{"@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#primaryimage"},"thumbnailUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742021235912180.png","datePublished":"2026-07-22T05:33:12+00:00","dateModified":"2026-09-28T02:48:42+00:00","description":"Partial discharge refers to the phenomenon of discharge that occurs between electrodes but does not penetrate them. It is caused by weaknesses in the insulation of electrical equipment or defects in the manufacturing process, leading to repeated breakdowns and extinguishing under high electric field intensity. This discharge manifests as breakdown of insulation gas, local breakdown of solid or liquid media within a small range, and local breakdown discharge caused by the concentration of electric field strength at the edges and corners of metal surfaces. Although the energy of this discharge is small, its short-term existence does not affect the insulation strength of electrical equipment. However, if partial discharge occurs continuously under the operating voltage of electrical equipment, these weak discharges will accumulate, gradually deteriorating the dielectric performance of insulation and enlarging local defects, ultimately leading to insulation breakdown.","breadcrumb":{"@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#breadcrumb"},"inLanguage":"de","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/"]}]},{"@type":"ImageObject","inLanguage":"de","@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#primaryimage","url":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742021235912180.png","contentUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/07\/1742021235912180.png","width":370,"height":276},{"@type":"BreadcrumbList","@id":"https:\/\/www.lstransformer.com\/whats-thepurpose-and-significance-of-partial-discharge-testing\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"\u9996\u9875","item":"https:\/\/www.lstransformer.com\/"},{"@type":"ListItem","position":2,"name":"What\u2019s the Purpose and Significance of Partial Discharge Testing"}]},{"@type":"WebSite","@id":"https:\/\/www.lstransformer.com\/#website","url":"https:\/\/www.lstransformer.com\/","name":"LS power Transformator, die Linie Reaktor, Hohe-Spannung Transformator, \u00d6l-eingetaucht Transformator-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","description":"","publisher":{"@id":"https:\/\/www.lstransformer.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.lstransformer.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"de"},{"@type":"Organization","@id":"https:\/\/www.lstransformer.com\/#organization","name":"LS power Transformator, die Linie Reaktor, Hohe-Spannung Transformator, \u00d6l-eingetaucht Transformator-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD","url":"https:\/\/www.lstransformer.com\/","logo":{"@type":"ImageObject","inLanguage":"de","@id":"https:\/\/www.lstransformer.com\/#\/schema\/logo\/image\/","url":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/06\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp","contentUrl":"https:\/\/www.lstransformer.com\/wp-content\/uploads\/2026\/06\/cropped-7e09bd7bad9c830e0d75b8487b0d77c3-1.webp","width":760,"height":202,"caption":"LS power transformer, Line reactor, High-voltage transformer, Oil-immersed transformer-CHANGSHA LUSHAN ELECTRONIC TECHNOLOGY CO.,LTD"},"image":{"@id":"https:\/\/www.lstransformer.com\/#\/schema\/logo\/image\/"}},{"@type":"Person","@id":"https:\/\/www.lstransformer.com\/#\/schema\/person\/674089c15f4857c19a997f886816d289","name":"369703005","image":{"@type":"ImageObject","inLanguage":"de","@id":"https:\/\/secure.gravatar.com\/avatar\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/dcaa0e47cd7b6c99ffdd80f5772032ed2d2591b5b8e7b905e5fd87a850954248?s=96&d=mm&r=g","caption":"369703005"},"url":"https:\/\/www.lstransformer.com\/de\/author\/369703005\/"}]}},"_links":{"self":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts\/1329","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/users\/3"}],"replies":[{"embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/comments?post=1329"}],"version-history":[{"count":5,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts\/1329\/revisions"}],"predecessor-version":[{"id":6756,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/posts\/1329\/revisions\/6756"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/media\/4191"}],"wp:attachment":[{"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/media?parent=1329"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/categories?post=1329"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.lstransformer.com\/de\/wp-json\/wp\/v2\/tags?post=1329"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}