Why Does Transformer Noise Persist? —From Noise Source Identification to Targeted Solutions

Inicio> Preguntas Frecuentes

Why Does Transformer Noise Persist? —From Noise Source Identification to Targeted Solutions

2025.06.07

Why Does Transformer Noise Persist?

—From Noise Source Identification to Targeted Solutions

 

According to the latest CIGRE survey, 29% of global operational transformers exhibit audible abnormal noise, with 18% of cases leading to equipment damage. Abnormal noise is not only an early sign of performance degradation but also a potential risk to grid safety. This guide integrates IEC 60076 and IEEE C57.12 standards to provide a systematic solution covering electromagnetic, mechanical, and environmental factors, offering actionable noise control strategies for global power enterprises.

 

Contenido

1. Electromagnetic System Abnormalities: Hidden Causes of Noise

Causas fundamentales 

 Magnetostriction Instability 

Silicon steel sheets generate periodic deformation (magnetostriction coefficient: 1-3 ppm) under alternating magnetic fields, with a vibration base frequency of twice the power frequency (100/120 Hz). When core clamping force drops below 15% of the design value, micro-movements between laminations trigger high-frequency resonance, increasing noise by 8-12 dB(A).

 

Comparación de datos:

Estado

Clamping Force (kN/m)

Ruido dB (A)

Para Tanque Empotrado o Alto

180 - 220

62±3

Anormal

<153

70 - 75

 

6


 Resonancia Armónica Risks Non-linear loads produce harmonic currents (especially 3rd and 5th orders). When harmonic distortion (THD) exceeds IEEE 519’s 5% limit, core vibration acceleration triples.

 

 Soluciones

Stepped Lamination Process Adopt a 45° core design to shift resonance peaks to non-sensitive frequencies (>800 Hz), reducing noise by 40%.

 

Dynamic Harmonic Suppression Install series filter reactors (6%/12% reactance) on the low-voltage side to increase harmonic path impedance (XL=2πfL), forcing harmonic current attenuation.

 

2. Mechanical Instability: Root of Progressive Noise

 Mecanismos de fallo

 Bolt Loosening Reacciona a la Cadena Per VDI 2230, M24 bolts lose 12%-18% preload annually. At <60% initial preload, structural components generate 200-500 Hz impact noise.

 

Criterio de inspección:

 

Parámetro

Desviación permitida

Consecuencias

Desplazamiento horizontal

<0.5 mm/m

Core eccentricity vibration

Vertical Settlement

<0.3 mm/m

Winding pressure imbalance

Angular Tilt

<0.1 °

resonancia estructural

 

Técnicas de refuerzo

 Self-Compensating Preload System Use DIN 2093 disc springs at critical joints to maintain ±5% preload fluctuation.

 Alineación láser Deploy API XD Laser systems for 0.001 mm precision to eliminate installation-induced noise.

 

2


3. Environmental Coupling: Overlooked Noise Amplifiers

 Análisis de escenario

 Ground Vibration Transmission Nearby roads/railways induce 30-80 Hz vibrations (ISO 10816 limit: 0.8 m/s²). At >1.2 m/s², vibrations transfer via rigid bases, increasing noise by 10 dB.

 

 Acoustic Reflection In enclosed substations, wall reflections boost specific frequencies by 4-6 dB. Optimize absorption layouts using COMSOL to reduce reverberation from 3.2s to 1.1s.

 

 Casos de estudio

 

Tipo de aislamiento

Frecuencia natural

Atenuación

Solicitud

Almohadillas de goma

8 15-Hz

60%

General environments

Resortes de aire

2 5-Hz

85%

Equipos de precisión

 

5


 Siemens Hamburg reduced traffic-induced noise from 68 dB to 57 dB using spring isolation (4 Hz).

 China Southern Grid cut acoustic reflections by 9 dB using porous aluminum fiber panels (NRC 0.95).

 

En resumen

Conclusion Transformer noise reflects imbalances in mechanical and electromagnetic energy. This guide’s "Electromagnetic-Structural-Environmental-Intelligent" framework enables systematic solutions:

 

Source Control: Optimize core design and harmonic suppression.

Propagation Blocking: Upgrade vibration isolation and absorption.

Smart Monitoring: Deploy IoT sensors and digital twins.

 

Implement quarterly ISO 10816 vibration scans and build an IEC 62485-compliant noise database to transition from reactive repairs to proactive maintenance.

 

Contáctenos

lushan, est.1975, es un fabricante profesional chino especializado en transformadores de potencia y reactores para50+ años. Los productos líderes son transformador monofásico, trifásico solo transformadores,transformador eléctrico,transformador de distribución, transformador reductor y elevador, transformador de baja tensión, transformador de alta tensión, transformador de control, transformador toroidal, transformador de núcleo R;Inductores de CC, reactores de CA, reactores de filtrado, reactores de línea y carga, bobinas, reactores de filtrado y productos intermedios de alta frecuencia.

 

Nuestro poder Los transformadores y reactores se utilizan ampliamente en 10 áreas de aplicación: tránsito rápido, maquinaria de construcción, energía renovable, fabricación inteligente, equipos médicos, prevención de explosiones en minas de carbón, sistema de excitación, sinterización al vacío (horno), aire acondicionado central.

 

Conozca más sobre transformadores de potencia y reactores:www.lstransformer.com.

 

Si desea obtener soluciones personalizadas para transformadores o reactancias, póngase en contacto con nosotros.

WhatsApp:+86 13787095096
Correo electrónico: marketing@hnlsdz.com