Why is it necessary to ground the transformer core? And why is it not advisable to use a multi-point grounding approach?

Отправляйте информацию о доставке на PayPal вместо выставления счета. > FAQ > Why is it necessary to ground the transformer core? And why is it not advisable to use a multi-point grounding approach?

Why is it necessary to ground the transformer core? And why is it not advisable to use a multi-point grounding approach?

微信分享

请复制下面链接,在微信内打开分享
https://www.lstransformer.com/fr/why-is-it-necessary-to-ground-the-transformer-core-and-why-is-it-not-advisable-to-use-a-multi-point-grounding-approach/

Why is it necessary to ground the transformer core? And why is it not advisable to use a multi-point grounding approach?

The core and its metal components generate different potentials due to their positions in the electric field. When the potential difference between two points reaches a level sufficient to break down the insulation between them, intermittent spark discharges occur. This discharge is intermittent, with the potential between the two points becoming equal after each discharge, causing the discharge to cease. Once a potential difference is reestablished, the discharge occurs again. This intermittent discharge can lead to the decomposition of transformer oil and potential damage to solid insulation, resulting in accidents. To prevent such occurrences, the core and other metal components (such as clamps and winding pressure plates) must be connected to the oil tank and grounded to ensure they are at the same potential (zero potential). If there are through-core screws on the core, they are effectively at the same potential as the core due to capacitive coupling, and separate grounding is not necessary.

Currently, a common grounding method involves placing a copper strip between the core laminations. Although there is insulation film between the core laminations, the entire core can still be considered grounded capacitively.

If the core is grounded at two points, it is equivalent to creating a short circuit on both sides of the core, resulting in a certain amount of current flow. This current leads to local overheating, increased losses, and may even cause the grounding strips to fuse, creating a suspended potential in the core, which is not allowed.

Therefore, the core must be grounded, and it should be done using a single grounding point.

Contact

LuShan, heure de l'est. 1975, est un fabricant professionnel Chinois spécialisé dans les transformateurs de puissance et des réacteurs de plus de 50 ans. Les produits de pointe sont transformateur monophasé, triphasé transformateurs d'isolement, transformateur électrique, transformateur de distribution, l'étape vers le bas et d'intensifier le transformateur de basse tension du transformateur, transformateur à haute tension, contrôle de transformateur toroïdal transformateur, transformateur R-core; inductances DC, AC réacteurs, le filtrage du réacteur, de ligne et de charge du réacteur, des bobines, le filtrage du réacteur, et intermédiaire, à haute fréquence produits.

Nos transformateurs de puissance et les réacteurs sont largement utilisés dans les 10 domaines d'application: transport en commun rapide, les machines de construction, les énergies renouvelables, intelligents de fabrication, des équipements médicaux, de la mine de charbon de l'explosion de la prévention, de l'excitation du système, frittage sous vide(four), d'une climatisation centrale.

En savoir plus sur transformateur de puissance et le réacteur: www.lstransformer.com.

Si vous souhaitez obtenir des solutions personnalisées pour les transformateurs ou des réacteurs, veuillez nous contacter.
WhatsApp:+86 13787095096
E-mail: marketing@hnlsdz.com

WhatsApp QR WeChat QR IVL 0.013mH-610A
Faire défiler vers le Haut