How is the External Withstand Voltage Test conducted?

Home > FAQ > How is the External Withstand Voltage Test conducted?

How is the External Withstand Voltage Test conducted?

微信分享

请复制下面链接,在微信内打开分享
https://www.lstransformer.com/how-is-the-external-withstand-voltage-test-conducted/

How is the External Withstand Voltage Test conducted?

undefined

The External Withstand Voltage Test is a one-minute AC high-voltage test conducted on the tested transformer, also known as the AC Withstand Voltage Test. This test is employed to assess the insulation performance between different winding sides and between windings and ground, specifically evaluating the main insulation of the transformer. Therefore, it is only applicable to fully insulated transformers. During the test, the different winding sides of the tested transformer are connected together, with one side subjected to voltage and the other side grounded, as illustrated in Figure 98-1.

During the External Withstand Voltage Test, the circuit should be closed when the power supply voltage is relatively low. The voltage ramp-up speed can be arbitrary when the test power supply voltage is below 40% of the test voltage. When it exceeds 40%, it should ramp up uniformly at a rate of 3% per second. Once the specified voltage and duration are reached, the voltage should be quickly and uniformly reduced to below 25% of the test voltage within 5 seconds before disconnecting the power supply.

Contact

LuShan, est. 1975, is a Chinese professional manufacturer specializing in power transformers and reactors for 50+ years. Leading products are single-phase transformer, three-phase isolation transformers, electrical transformer, distribution transformer, step down and step up transformer, low voltage transformer, high voltage transformer, control transformer, toroidal transformer, R-core transformer; DC inductors, AC reactors, filtering reactor, line and load reactor, chokes, filtering reactor, and intermediate, high-frequency products.

Our power transformers and reactors are widely used in 10 application areas: rapid transit, construction machinery, renewable energy, intelligent manufacturing, medical equipment, coal mine explosion prevention, excitation system, vacuum sintering(furnace), central air conditioning.

Know more about power transformer and reactor: www.lstransformer.com.

If you would like to obtain customized solutions for transformers or reactors, please contact us.
WhatsApp:+86 13787095096
Email: marketing@hnlsdz.com

WhatsApp QR WeChat QR sales@hnlsdz.com
Scroll to Top