Insulation level and temperature rise:

The insulation level of a transformer refers to the maximum allowable temperature rise, which is the heat resistance level of the insulation material used in the transformer. The temperature rise, on the other hand, refers to the temperature difference between the inside of the transformer and its surrounding environment.

The insulation level of transformers is classified into different levels, such as A, E, B, F, and H. Each insulation level corresponds to a different maximum allowable temperature rise limit. For example, the A-level insulation winding temperature rise limit is 60K, the E-level insulation winding temperature rise limit is 75K, the B-level insulation winding temperature rise limit is 80K, the F-level insulation winding temperature rise limit is 100K, and the H-level insulation winding temperature rise limit is 125K.

Insulation class maximum allowable temperature(℃) Winding temperature rise limit (K) Performance reference temperature(℃)
A 105 60 80
E 120 75 95
B 130 80 100
F 155 100 120
H 180 125 145

In summary

The insulation level of a transformer determines its heat resistance level, and the temperature rise limit sets the maximum allowable temperature difference between the inside of the transformer and its environment.

Contact

LuShan, est. 1975, is a Chinese professional manufacturer specializing in power transformers and reactors for 50+ years. Leading products are single-phase transformer, three-phase isolation transformers, electrical transformer, distribution transformer, step down and step up transformer, low voltage transformer, high voltage transformer, control transformer, toroidal transformer, R-core transformer; DC inductors, AC reactors, filtering reactor, line and load reactor, chokes, filtering reactor, and intermediate, high-frequency products.

Our power transformers and reactors are widely used in 10 application areas: rapid transit, construction machinery, renewable energy, intelligent manufacturing, medical equipment, coal mine explosion prevention, excitation system, vacuum sintering(furnace), central air conditioning.

Know more about power transformer and reactor: www.lstransformer.com.

If you would like to obtain customized solutions for transformers or reactors, please contact us.
WhatsApp:+86 13787095096
Email: marketing@hnlsdz.com

WhatsApp QR WeChat QR sales@hnlsdz.com
Scroll to Top