What is a split winding? What are its requirements?

A split winding refers to the division of the low-voltage winding of a transformer into multiple parts that are electrically independent. These divided low-voltage winding sections are each connected to two generators, allowing each generator to operate independently or simultaneously. In the event of a failure in one generator, the other generator can continue to operate normally. Such a winding is known as a dual split winding, where each split winding section has a capacity equal to half of the transformer’s total capacity. The split winding can also be arranged in a radial split configuration (low-high-low arrangement).

If the low-voltage winding is split into three parts, with no electrical connections between them, and each part can be connected to a separate generator, it is referred to as a three-split winding. The capacity of each split winding section in this case is one-third of the transformer’s total capacity.

The requirements for a split winding are as follows:

(1) The various branches of the split winding in an up-transformer must have a sufficiently large total impedance to ensure that a generator failure does not cause another generator to shut down. This high impedance helps limit the short-circuit current from flowing into the other generator.

(2) The total impedance between the branches of the split winding and other non-split windings must be balanced.

(3) In a three-phase axial split transformer, each column of the high-voltage winding must be connected in parallel vertically, while a single-phase transformer can have two columns of high-voltage winding connected in parallel. This arrangement ensures that each branch of the split winding can continue to operate if one or two branches are disconnected. Surge arresters are used to protect the operating branches.

(4) Branches of split windings with the same rated voltage should be able to operate in parallel.

(5) The insulation structure between the various parts of the split winding and other windings must have sufficient electrical strength. This is necessary because a significant induced voltage can occur between adjacent terminals when an impulse voltage acts on the high-voltage winding.

(6) Split impedance voltage: For a single-phase dual split winding, the split impedance voltage is four times that of the impedance voltage for a non-split dual winding. In the case of a three-phase axial dual split, the split impedance voltage is approximately 3.5 times that of the impedance voltage for a non-split dual winding. The impedance voltage of a split transformer can be calculated using the impedance voltage calculation method for non-split windings, with the final impedance voltage multiplied by the specified factors.

(7) A split transformer must be able to withstand the mechanical forces generated by short-circuit currents.

indefinido

Contacto

LuShan, est. En 1975, es un Chino fabricante profesional que se especializa en los transformadores de potencia y reactores de más de 50 años. Los productos principales son transformador monofásico, trifásico de transformadores de aislamiento, transformador eléctrico, transformador de distribución, el paso hacia abajo y paso transformador de baja tensión del transformador, transformador de alto voltaje, transformador de control, transformador toroidal, R-transformador con núcleo; DC inductores, CA reactores, filtrado de reactor de línea y de carga del reactor, estrangulaciones, el filtrado de los reactores y de los intermedios, de alta frecuencia de los productos.

Nuestros transformadores de potencia y reactores son ampliamente utilizados en las 10 áreas de aplicación: rapid transit, maquinaria de construcción, energía renovable, de fabricación inteligentes, equipos médicos, la mina de carbón de la explosión de la prevención, el sistema de excitación, de vacío, de sinterización(horno), aire acondicionado central.

Saber más acerca de transformadores de potencia y reactores: www.lstransformer.com.

Si desea obtener soluciones personalizadas para transformadores o reactores, póngase en contacto con nosotros.
WhatsApp:+86 13787095096
Correo electrónico: marketing@hnlsdz.com

WhatsApp QR WeChat QR sales@hnlsdz.com
Desplazarse a la parte Superior