Vacuum epoxy resin cast transformers are widely used due to their various advantages, including low noise, low partial discharge, high reliability, and long service life. To ensure the safe and stable operation of these transformers, several tests need to be conducted before putting them into operation.

(1) Insulation resistance test:

This test is performed to ensure the proper insulation resistance of the transformer windings. A megger is used to measure the insulation resistance between the winding and ground. The recommended value for insulation resistance is 1 megaohm or higher.

(2) Ratio test:

The ratio test is conducted to verify the turns ratio of the transformer. The actual turns ratio is measured and compared with the design specification.

(3) Polarity test:

The polarity test is performed to determine the polarity of the transformer windings. This test is essential to ensure that the transformer windings are correctly connected.

(4) Winding resistance test:

The winding resistance test is performed to determine the resistance of the transformer windings. This test is used to check the correctness of the transformer design and to identify any faulty winding.

(5) No-load loss and excitation current test:

The no-load loss and excitation current test is conducted to determine the no-load loss and excitation current of the transformer. These values are important for calculating the efficiency of the transformer.

(6) Load loss and impedance voltage test:

The load loss and impedance voltage test is conducted to determine the load loss and impedance voltage of the transformer. These values are essential for calculating the regulation and efficiency of the transformer.

(7) Insulation level test:

The insulation level test is conducted to determine the insulation strength of the transformer. This test is essential to ensure the transformer’s ability to withstand the specified voltage without any insulation failure.

In conclusion, these tests are essential to ensure the safe and reliable operation of vacuum epoxy resin cast transformers. Properly conducted tests can detect any faults or defects in the transformer, enabling corrective measures to be taken before putting the transformer into operation.

Additionally, before commissioning, the vacuum epoxy casting transformer should undergo insulation resistance tests, oil pressure tests, and dielectric strength tests to ensure that it meets the safety and performance standards. These tests help to identify any potential issues and ensure that the transformer is functioning correctly before being put into operation.

Contacto

LuShan, est. En 1975, es un Chino fabricante profesional que se especializa en los transformadores de potencia y reactores de más de 50 años. Los productos principales son transformador monofásico, trifásico de transformadores de aislamiento, transformador eléctrico, transformador de distribución, el paso hacia abajo y paso transformador de baja tensión del transformador, transformador de alto voltaje, transformador de control, transformador toroidal, R-transformador con núcleo; DC inductores, CA reactores, filtrado de reactor de línea y de carga del reactor, estrangulaciones, el filtrado de los reactores y de los intermedios, de alta frecuencia de los productos.

Nuestros transformadores de potencia y reactores son ampliamente utilizados en las 10 áreas de aplicación: rapid transit, maquinaria de construcción, energía renovable, de fabricación inteligentes, equipos médicos, la mina de carbón de la explosión de la prevención, el sistema de excitación, de vacío, de sinterización(horno), aire acondicionado central.

Saber más acerca de transformadores de potencia y reactores: www.lstransformer.com.

Si desea obtener soluciones personalizadas para transformadores o reactores, póngase en contacto con nosotros.
WhatsApp:+86 13787095096
Correo electrónico: marketing@hnlsdz.com

WhatsApp QR WeChat QR sales@hnlsdz.com
Desplazarse a la parte Superior