Comparison of the Four Core Partial Discharge Detection Technologies: In-Depth Analysis of Principles, Advantages, and Applications

ホーム > FAQ > Comparison of the Four Core Partial Discharge Detection Technologies: In-Depth Analysis of Principles, Advantages, and Applications

Comparison of the Four Core Partial Discharge Detection Technologies: In-Depth Analysis of Principles, Advantages, and Applications

微信分享

请复制下面链接,在微信内打开分享
https://www.lstransformer.com/ja/comparison-of-the-four-core-partial-discharge-detection-technologies-in-depth-analysis-of-principles-advantages-and-applications/

Comparison of the Four Core Partial Discharge Detection Technologies: In-Depth Analysis of Principles, Advantages, and Applications

In the field of safety maintenance for high-voltage electrical equipment, Partial Discharge Detection (PD Detection) plays a critical role as an early warning system. As global power grids demand higher reliability for key assets such as transformers and reactors, mastering accurate and efficient PD detection technologies has become an industry consensus. This guide provides a detailed analysis of the four mainstream international detection methods: the Pulse Current Method (IEC 60270 Standard), Ultrasonic Method (Acoustic Emission), Ultra-High Frequency (UHF) Method, and Transient Earth Voltage (TEV) Method, helping you develop a scientific equipment health management strategy.

コンテンツ

1. Pulse Current Method (IEC 60270 Standard Method) – The Gold Standard for Reference

2

1.1 Core Principle: Electromagnetic Induction for Quantitative Captur

The Pulse Current Method adheres to the IEC 60270                         international standard and is the benchmark for PD   quantification. This method detects transient current pulses  caused by partial discharges by connecting a precision detection impedance (Zm) in series with the equipment’s grounding wire or coupling capacitor (Ck). When a discharge occurs within the insulation, rapid charge migration generates a sudden current change (di/dt).●According to Faraday’s Law of Electromagnetic Induction:

V(t) = M × di/dt

Here, V(t) is the transient voltage across the detection impedance, and M is the mutual inductance coefficient of the measurement circuit.

Using a high-speed acquisition system to record the V(t) waveform, the Apparent Charge (Q) can be precisely calculated:

Q = ∫i(t)dt ≈ (1/R) × ∫V(t)dt

where R is the resistive component of the detection impedance

In-Depth Analysis of Advantages and Limitations

側面 Description Case Study
Advantages ▪ Only method that directly measures apparent charge (in pC) ▪ Complies with IEC 60270 standard ▪ Lab precision up to 0.1pC Siemens factory detected 3pC floating discharge in a 400kV transformer during factory testing, preventing field failure.
Limitations ▪ Susceptible to electromagnetic interference (especially <1MHz) ▪ Requires disconnecting grounding for sensor installation ▪ Cannot locate PD sources A substation recorded 200% inflated readings due to inverter interference, requiring a 300kHz bandpass filter for correction.
Applications ▪ Factory acceptance tests (IEC 60076) ▪ Lab calibration ▪ Offline diagnostics Brazil’s Itaipu Dam uses this method annually to calibrate online monitoring systems, maintaining ±5% error margins.

2. Ultrasonic Method (Acoustic Emission) – The Mechanical Wave Localization Expert

3

2.1Core Principle: Tracking Acoustic Wave Propagation Paths

Partial discharges generate micro-explosions, producing mechanical vibrations (20kHz-300kHz). Piezoelectric sensors placed on the equipment surface capture these signals. The system uses Time of Flight Difference (TOFD) for 3D localization:

∆t = (d1 – d2)/v

Here, v is the wave speed in the medium (~1400m/s in oil, ~2400m/s in epoxy)

∆t is the arrival time difference between sensors.

In-Depth Analysis of Advantages and Limitations

側面 Description Engineering Solutions
Advantages ▪ Spatial accuracy ±10cm ▪ Detects mechanical defects (e.g., loosening, deformation) ▪ Strong EMI resistance BC Hydro (Canada) located loose bolts inside a transformer, preventing winding deformation.
Limitations ▪ High attenuation in oil (2dB/m at 150kHz) ▪ No discharge quantification ▪ Requires couplant Tokyo Electric Power developed multi-layer sensor arrays, improving deep-discharge detection by 40%.
Applications ▪ PD source localization in transformers/reactors ▪ GIS mechanical fault diagnosis ▪ Bushing defect detection A Chinese UHV substation found displacement in a converter transformer’s grading ring, with only 8cm error.

6

3. Ultra-High Frequency (UHF) Method – The Electromagnetic Wave “X-ray”

3.1 Core Principle: Capturing GHz-Band Electromagnetic Pulses

PD generates steep current pulses (rise time <1ns),                emitting 300MHz-3GHz electromagnetic waves. Built-in UHF sensors (e.g., Archimedean spiral antennas) inside equipment (e.g., transformer tanks, GIS chambers) detect these signals.

In-Depth Analysis of Advantages and Limitations

側面 Description Field Data
Advantages ▪ 20-40dB higher SNR ▪ Identifies discharge types via PRPD patterns ▪ Ideal for online monitoring UK National Grid measured 35dB SNR with UHF vs. 12dB for Pulse Current Method in 400kV GIS.
Limitations ▪ 4dB/m attenuation at 3GHz in oil ▪ Requires pre-installed sensors ▪ Needs on-site calibration Saudi Arabia’s Neom project cut installation time to 15 minutes/unit with valve-mounted UHF probes.
Applications ▪ GIS online PD monitoring ▪ Transformer-embedded systems ▪ Cable termination inspection France’s RTE achieved <0.5% false alarms over 5 years with 345kV transformer UHF systems.

4. Transient Earth Voltage (TEV) Method – The Rapid External Diagnostic Solution

4.1 Core Principle: Electromagnetic Coupling at Metal Interfaces

PD near grounded shields induces nanosecond transient voltages on metal surfaces. Capacitive probes detect these Transient Earth Voltages (typically <1V):

V_tev = k × (dQ/dt) × Z_c

Here, k is the coupling coefficient

 Z_c is the surface wave impedance (80-150Ω).

In-Depth Analysis of Advantages and Limitations

側面 Description Case Study
Advantages ▪ Fast (>10 points/minute)

▪ No power outage needed

▪ 70% lower cost than other methods

Dubai Airport screened 128 switchgear panels in 2 hours, finding 3 faults.
Limitations ▪ Surface-only (3dB/cm attenuation)

▪ No discharge quantification

▪ Humidity-sensitive

Singapore developed humidity-compensation algorithms, cutting false alarms from 25% to 8%.
Applications ▪ Switchgear rapid inspection

▪ Transformer tank assessment

▪ Distribution room checks

Australian mines slashed maintenance costs by 52% using TEV for 400 devices.
Technology Decision Matrix: Key Factors for Application Matching
Evaluation Criteria Pulse Current Ultrasonic UHF TEV
Quantification ★★★★★ ★★☆ ★★★☆ ★★☆
Localization N/A ★★★★★ ★★★★☆ ★★☆
Noise Immunity ★★☆ ★★★☆ ★★★★★ ★★★☆
Installation Ease Requires circuit access Needs surface mounting Built-in probes Surface contact
Best For Offline tests Oil-immersed equipment GIS/Transformers Switchgear

概要

Global best practices (e.g., CIGRE WG D1.37) show that single-method solutions struggle with complex scenarios. Leading systems now adopt multi-modal data fusion:

Pulse Current + UHF:Combines quantification and noise immunity (e.g., ABB Guardus).

Ultrasonic + TEV:Enables fast switchgear PD localization (e.g., Omron PD-TEV).

AI-Driven Diagnostics:Uses IEEE Std C57.104 and machine learning (e.g., PSO-SVM models).

PG&E (USA) reported that UHF-ultrasonic fusion extended transformer fault warnings by 37 days and cut costs by 52%.

With IEC 62478 (UHF) standardization and AI advancements in PD pattern recognition, the field is evolving toward higher precision and smarter diagnostics. Follow updates from IEEE Dielectrics and Electrical Insulation Society for cutting-edge trends.

Global grid stability begins with precise detection of microscopic discharges. When these four technologies form a diagnostic network, every captured pulse and analyzed sound wave rewrites the future of electrical reliability—leaving no room for unexpected failures.

連絡先

廬山,est。 1975年には中国の専門職の専門メーカーの電力変圧器及び原子炉のための50+る。 主製品 単相トランス、三相絶縁変圧器、電気トランス、物流トランス、ステップの下、信用リスク以外のリスクにつきトランス、低電圧トランス、高電圧トランス、制御トランス、トロイダルトランス、Rコアトランス直流インダクター、AC炉では、フィルタリング炉、負荷炉chokes、フィルタリングの原子炉は、中間体、高周波製品.

当社の電力変圧器及び原子炉に広く使用されて10アプリケーション:高速鉄道、建設機械、再生可能エネルギー、ロボット、医療機器、炭鉱爆発の防止、励起システム、真空焼結(炉)、中央エアコンがあります。

知電源トランス原子炉: www.lstransformer.com.

希得のカスタマイズソリューションのためのトランスや原子炉、お問い合わせください。
WhatsApp:+86 13787095096
メール:marketing@hnlsdz.com

WhatsAppにQR WeChat QR sales@hnlsdz.com
スクロールトップ