How to Look at The Parallel Operation of Transformers?

ホーム > FAQ > How to Look at The Parallel Operation of Transformers?

How to Look at The Parallel Operation of Transformers?

微信分享

请复制下面链接,在微信内打开分享
https://www.lstransformer.com/ja/how-to-look-at-theparalleloperation-of-transformers%ef%bc%9f/

How to Look at TheParallelOperation of Transformers?

The parallel operation of transformers refers to connecting the primary windings of two or more transformers to a common busbar and connecting their secondary windings to a common secondary busbar. Transformers operated in this manner are termed to be in parallel operation.

1. Advantages of parallel operation of transformers include:

(1) Meeting Demands of Large Power Grids:

Addresses the capacity requirements that a single transformer may find challenging to meet in a large power grid.

(2) Enhancing Power Supply Reliability:

Improves the reliability of power supply; if one transformer experiences a fault and is disconnected, others can continue supplying power.

(3) Adjusting Transformer Quantity Based on Load:

Allows for adjusting the number of transformers in operation according to the load, reducing losses and improving the economic operation of the power grid.

(4) Facilitating Scheduled Maintenance:

Facilitates scheduled maintenance of transformers.

(5) Reducing One-Time Investments in Power Plants and Substations :

Reduces the one-time investments required for power plants and substations.

2. Conditions and allowable deviation ranges for the parallel operation of transformers are as follows:

(1) Matching Connection Groups:

The connection groups must be the same; otherwise, it could lead to the generation of undesired circulating currents between parallel transformers.

(2) Matching Rated Voltage Ratios and Rated Voltages:

The rated voltage ratios and rated voltages of each transformer must be the same to minimize the occurrence of circulating currents.

(3) Allowable Deviation in Rated Impedance Voltage:

The allowable deviation in rated impedance voltage is ±10%. In practice, even if the rated impedance voltage values are not identical, transformers with similar actual values can still be operated in parallel. The load distribution is inversely proportional to the impedance voltage, favoring the operation of transformers with lower impedance voltage under full load, thereby optimizing operational efficiency.

連絡先

廬山,est。 1975年には中国の専門職の専門メーカーの電力変圧器及び原子炉のための50+る。 主製品 単相トランス、三相絶縁変圧器、電気トランス、物流トランス、ステップの下、信用リスク以外のリスクにつきトランス、低電圧トランス、高電圧トランス、制御トランス、トロイダルトランス、Rコアトランス直流インダクター、AC炉では、フィルタリング炉、負荷炉chokes、フィルタリングの原子炉は、中間体、高周波製品.

当社の電力変圧器及び原子炉に広く使用されて10アプリケーション:高速鉄道、建設機械、再生可能エネルギー、ロボット、医療機器、炭鉱爆発の防止、励起システム、真空焼結(炉)、中央エアコンがあります。

知電源トランス原子炉: www.lstransformer.com.

希得のカスタマイズソリューションのためのトランスや原子炉、お問い合わせください。
WhatsApp:+86 13787095096
メール:marketing@hnlsdz.com

WhatsAppにQR WeChat QR sales@hnlsdz.com
スクロールトップ