Wie ist die Messung des Isolationswiderstandes und der absorption ratio durchgeführt?
How is the measurement of insulation resistance and absorption ratio conducted? Insulation resistance, denoted as R, is typically determined by applying a voltage of 2500V for 60 seconds and measuring the resulting value using a megohmmeter with a maximum range of 10000 MQ. Due to variations in the stability of...
測定により無負荷電圧と無負荷電流を得ついて包括的に理解するためにトランス設計、製造、品質を評価するために、その電磁性能および運用の状況、および提供のための科学的基盤の最適化設計、生産プロセスの改善などを組み立て品質、効果的なメンテナンス。 正確な負荷特性の測定に必要な確保のためのトランスの性能-信頼性への貢献全体の品質向上と運用効率トランス.
How is the measurement of winding resistance conducted? When measuring winding resistance, both the bridge method and voltage drop method are employed. For resistance values exceeding 100, a single-arm bridge is utilized, while for values below 102, a double-arm bridge is employed. In the voltage drop method, a power source...
What are the common electrical tests for transformers?
What are the common electrical tests for transformers? Conventional electrical tests for transformers are designed to identify internal faults and primarily include the following: (1) Voltage Ratio Test: Used to verify the voltage ratio and determine if there are short circuits between turns or layers, or if switch leads are...
How to conduct a pump test for oil-immersed transformers?
How to conduct a pump test for oil-immersed transformers? Performing a pump test for oil-immersed transformers is an essential step in the production and maintenance processes. For transformers that have completed the assembly, especially those with a capacity of 8000kVA, voltage of 35kV and below, and equipped with an oil...
How to perform oil leak repair?
How to perform oil leak repair? To achieve oil welding repair, the following measures can be taken: (1) Selection of Welding Method for Oil Leak Repair: Considering the characteristic of rapid heat dissipation in oil leak repair, arc welding should be used for repairs instead of gas welding. (2) Pre-treatment...
Können Transformatoren geschweißt werden mit öl für die Reparatur?
Can transformers be welded with oil for repair? The repair of oil leakage in transformer welding lines is a crucial task for operating personnel. If welding repairs are conducted during a power outage with oil drainage, the transformer body remains inside the oil tank. As the insulation on the transformer...
の無負荷電流ベクトルの合計のコア損失引当金流動の励磁電流とその大きさにより、コアの磁ます。 測定により無負荷電流で評価し、透磁率、ヒステリシス損失、および渦電流損失の材料を決定するかどうかを核に素材、加工に必要です。
Why is it necessary to fill nitrogen and dismantle components such as casings during transportation? And why is it required to remove the oil storage tank and safety duct during vacuum oil injection? When the transport weight of a large transformer exceeds the carrying capacity of the transport vehicle, it...
Was sind die Merkmale der drei häufigsten verwendete Wicklung Konfigurationen, die in Transformatoren?
What are the characteristics of the three commonly used winding configurations in transformers? (1) Y-shaped winding characteristics: The Y-shaped winding has a winding current equal to the line current, with a larger wire cross-section, providing excellent mechanical strength. The winding voltage is equal to 1/√3 times the line voltage, resulting...
Was sollte beachtet werden beim Schweißen führt bei Transformatoren mit einer Spannung von 60kV und oben?
What should be noted during the welding of leads for transformers with a voltage of 60kV and above? When welding leads for transformers with a voltage of 60kV and above, the following precautions should be taken: Before welding the leads, it is essential to wrap the base of the leads...
Wie ist die Heißluft-Trocknung unter Vakuum Methode durchgeführt?
How is the hot air vacuum drying method conducted? The hot air vacuum drying method is currently a widely adopted process. In this method, hot air with a temperature ranging from 105 to 130°C is introduced into a vacuum tank to heat the apparatus, ensuring uniform heating of its interior...
Wie wirkt sich die Höhe auf den Betrieb von Transformatoren?
What impact does altitude have on the operation of transformers? In areas where the altitude does not exceed 1000 meters, transformers can operate without considering the altitude factor. However, in regions with altitudes above 1000 meters, transformers must take into account the impact of thin air on heat dissipation and...
Wie ist der Schutz der Blitzableiter an den Sternpunkt des Transformators durchgeführt?
How is the protection of the lightning arrester at the neutral point of the transformer carried out? For transformers operating in a system with an effectively grounded neutral point, if the neutral point is not grounded, a lightning arrester should be installed at the neutral point. Similarly, for transformers operating...