接続部の三相トランス

Connection section of Three-Phase Transformers Three-phase transformers are widely used in power systems to step up or step down the voltage levels in three-phase circuits. The connection of the three-phase transformer windings determines the output voltage and current characteristics of the transformer. There are several types of connection groups for three-phase transformers, each with different advantages and disadvantages. The three most common connection groups for three-phase transformers are Y-Y, Delta-Delta, and Y-Delta. The Y-Y connection group consists of three windings connected in a Y configuration on both the primary and secondary sides. This connection group provides a neutral point on both the primary and secondary sides, which can be used

FAQ

の温度制御システムのための乾式トランス?

What are the temperature control systems for dry-type transformers? The safe operation and service life of dry-type transformers largely depend on the safety and reliability of the winding insulation. Exceeding the insulation withstand temperature due to winding temperature can lead to insulation damage, which is one of the main reasons why transformers cannot function properly. Therefore, monitoring and alarm control of the operating temperature of transformers are crucial. (1) Automatic Fan Control: Temperature signals are obtained by Pt100 thermal resistance buried in the hottest part of the low-voltage winding. As the load on the transformer increases and the operating temperature rises, the fan cooling system is automatically activated when the

FAQ

が入るのはなぜ多くのベントプラグ、ガス-ガイドパイプは、トランス? なぜ油から注入されたのはタンク底部?

Why are there so many vent plugs and gas guide pipes on a transformer? Why is oil injected from the bottom of the tank? Vent plugs are commonly installed on the radiator, lifting platform, oil storage tank, and casing of transformers. This is because if vent plugs are not installed, air bubbles will be trapped at the top when oil is injected from the bottom of the tank, creating dead spots. These bubbles, if left inside the transformer, can easily lead to discharges. If they are trapped in the radiator, it can affect the oil flow and, consequently, the heat dissipation efficiency. Due to the varying installation heights and structures

FAQ

どのように選べるトランスによる電気負荷?

How to Choose Transformers According to Electrical Load? The capacity of distribution transformers should consider the facility capacity of various electrical equipment, calculate the load (generally excluding fire loads), and the compensated apparent capacity is the basis for selecting the capacity and quantity of transformers. The load rate of general transformers is around 85%. This method is relatively simple and can be used for estimating capacity. According to GB/T17468-1998 “Guidelines for Selection of Power Transformers,” the selection of distribution transformer capacity should be determined based on GB/T17211-1998 “Guidelines for Load of Dry-Type Power Transformers” and calculated load. The above two guidelines provide computer programs and normal periodic load charts to

FAQ

する上で考慮すべき選択-利用ブッシュ?

What should be considered when selecting and using bushings? When selecting and using bushings, certain considerations need to be taken into account. Bushings, as current-carrying components of transformers, directly impact the insulation performance of transformers. Here are the key points to be aware of during selection and usage: (1) Ambient Medium Temperature: For oil-immersed transformers, the temperature of the bushings in the oil is related to the temperature rise of the upper oil layer. In the case of self-cooling and forced-air cooling, the temperature rise of the upper oil layer is 55K, thus allowing a temperature rise of 15K for the lower terminal. In the case of strong oil-air cooling,

FAQ

の異なる接続とその影響を摺動コアトランスインピーダンス特性

A Look at the Different Connections and Their Effects on Sliding Core Transformer Impedance Characteristics The impedance characteristics of a sliding core transformer are determined by the various connecting configurations of the windings. The delta connection provides the lowest change in impedance per unit of current. This makes the delta connection desirable for higher voltage applications when a reliable, low impedance path for current is desired. The star connection creates a high impedance for the same current, which is beneficial for reducing harmonic distortion and maintaining a stable output voltage in low voltage applications. The Y connection is a combination of the two, creating a balance between reliability and stability.

FAQ

どのような地質環境に影響を与える操作のトランス?

How does the geological environment impact the operation of transformers? The primary consideration is the transformer’s ability to withstand earthquakes. Under normal operating conditions, it is stipulated that the horizontal acceleration of the ground should be less than 0.3g, and the vertical acceleration should be less than 0.15g. When installing transformers in seismically active zones, it can be specified during the ordering process the Richter seismic intensity that the transformer should be able to withstand. Regarding the internal structure of transformers, it has been designed with a focus on secure fixation during transportation and the ability to withstand mechanical stress caused by short-circuit currents. Therefore, the internal components are not

FAQ

の巻線に接続するための三相トランス?

What are the most common winding connections for a three-phase transformer? The most common winding connections for a sliding core transformer are the delta, star, and Y-connections. The delta connection is typically used for higher voltage applications, as it provides a low impedance path for the current to flow. The star connection is used for low voltage applications and has fewer negative effects on the output voltage waveform. The Y connection is a combination of delta and star connections and is used when a stable output voltage is desired. These three connections are the most common used in sliding core transformers, although other more complex connections are possible. The delta

FAQ

何のメリット単相トランス?

What are the advantages of single-phase transformers? Less material usage: Single-phase transformers require 20% less iron and 10% less copper compared to three-phase transformers of the same capacity. Particularly when using a wound iron core structure, the no-load losses of the transformer can be reduced by more than 15%. This reduction in material usage leads to decreased manufacturing and operational costs, ultimately resulting in optimal life cycle costs. Lower line investment: Implementing a single-phase power supply system in the grid can save 33% to 63% of conductors. Calculated based on economic current density, this can save 42% of conductor weight, and based on mechanical strength, it can reduce conductor consumption

FAQ

維持及び運営の連絡調節トランス

Maintaining and Operating a Contact Regulating Transformer In order to ensure the proper operation and maintenance of a contact regulating transformer, it is important to understand the basic principles and components involved. The primary components of the transformer are the contact coil, two arms, and two contact electrodes. The contact coil is connected to the arms, while the contact electrodes are connected to the DC power supply. When running and maintaining a contact regulating transformer, it is important to keep the contact electrodes clean and free of any debris or corrosion. This can be achieved through regular cleaning and inspection. It’s also important to check that the arms are properly